Model SP-AL(NC) - Manufacturer Specifications
| |
|
SELECTABLE CURRENT INPUT RANGES A.C. Amps, RMS |
|
1.5-50, 50-100, 100-200 |
|
SPECIFICATIONS |
Opening Size |
0.82" x 0.86" |
Max Weight (unit) |
4.5 oz |
Screw Terminals |
14 to 22 AWG |
Switch Rating |
0.3A@135V AC/DC |
Operating Temperature |
-30°C to 70°C |
Operating Humidity |
0-95% RH non-condensing |
Isolation Voltage |
2000 Volts |
Frequency |
40 to 400 Hz |
|
|
SETTING THE TRIP VALUE: |
- Using the jumper, select the proper range:
1.5-50, 50-100, or 100-200.
- All devices are factory set at the minimum switch point.
- To INCREASE the set point while the monitored load is on, turn the adjustment CLOCKWISE until the output switches as indicated by the status LED light or voltmeter connected across the device output terminals.
- Turn the adjustment slightly back COUNTERCLOCKWISE past the point to insure normal line current variations do not cause false conditions.
|
|
Manufacturer reserves the right to change specifications without notice.
|
|